Guide · updated November 19, 2026

Replacing electric baseboard heat with a heat pump

Ductless heat pumps for Ontario houses with no furnace, the higher rebate tier, and the sizing limit for electrically heated homes.

Electric baseboards put a house in the higher Home Renovation Savings tier and, very often, in a house with no ducts. Both facts should be on the quote before anyone talks about a furnace-shaped heat pump.

The rebate

Electricity is grouped with oil, propane, and wood: up to $7,500 for cold-climate air-source equipment at $1,250 per ton at 8.3°C, and up to $12,000 for ground-source at $2,000 per ton of closed-loop capacity. You own the home, the home is an eligible building, the power is Ontario’s grid, and this is the first heat pump that heats the place. A rented system uses the $2,000 air-source cap instead.

In this region the grid utilities are Enova Power in Kitchener and Waterloo, GrandBridge Energy in Cambridge, and Alectra in Guelph. Those are Ontario distributors. The Cornwall Electric exception does not describe these cities.

You may keep the existing electric heat as backup. The help page says so. The baseboards do not become a rebate.

Ductless is an eligible shape

The stream requirements allow centrally ducted systems and ductless or partly ducted mini-splits, including multi-head systems, if the heat actually gets to the rooms. For a mini-split, both the indoor and outdoor units have to be installed. Replacing one of them, or adding a head to a system you already have, is not the rebate.

Electrically heated homes are limited to NRCan sizing options C and D if they want the incentive. Those are the options aimed at most of the heating load, not a single head that takes the chill off one room while baseboards do the rest. If the quote shows one head for a whole house, ask how that meets option C or D. If the honest answer is that it does not, either add heads or stop calling it a rebate job.

Panel and placement

Some baseboard houses already have a large service because the baseboards were the heating load. Some do not. The quote should say what the panel can take and whether a service upgrade is included. We do not estimate amperage from the sidewalk.

Heads need a wall, a place for condensate, and a line-set route that does not wreck the trim in a house you like. Outdoor units need clearance and a spot above the snow you actually get. None of that is in the rebate table.

If the house already has a ductless heat pump that heats, you are done with this rebate. The first-heat-pump rule does not reset because the heads are old. See the first-heat-pump rule.

To ask for a price, use the quote form and write “no ducts, baseboard” in the notes.